 ..6 Over-current of the compressor
Outdoor Display: LED1 flash 3 or 24 or 25 times
The current of the compressor is too high
when the IPM Module is damaged
or the compressor is damaged.
power supply voltage is too low or too high
Faulty IPM Module
Faulty compressor
Faulty power supply
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
parts damage may be occurred.
Electrify the machine again and turn it on
with the remote controller, If malfunctions
are reported before or upon the compresso
r
being started up,
IPM Module is damaged and
needs replacing.
Repair the power supply
The system may have been over or under
charged with gas, which can be judged through
the pressure of the measuring system.
YES
NO
Yes
NO
The compressor is started normally, but
malfunctions are reported after it has
run for some time. Check the powe
r
supply is too low or too high
NO
Service diagnosis
Domestic air conditioner

Conditions
Supposed
Causes
Troubleshooting
Method of
malfunction detection
Malfunction detection
conditions