..12 High work-intense protection
Outdoor display LED1 flash 21 times
High work-intense control is activated in the heating mode if the temperature
being sensed by the heat exchanger thermistor exceeds the limit.
Activated when the temperature being sensed by the heat exchanger
rises above 65ć twices in 30 minutes.
Ƶ
Faulty electronic expansion valve
Ƶ
Dirty heat exchanger
Ƶ Faulty heat-exchange sensor
Ƶ Insufficient gas
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the
remote controller, check whether the wind
temperature is below 65ć
The malfunction is reported
after the machine has run
for some time?
1 ǃ Check room temperature and
pipe temperature sensor.
2ǃthe temperature monitoring circuit
of the indoor mainboard
The indoor unit blows poorly
due to blocked filters or poor
condition of the fan?
1) Clean the filters
2) Reinstall the fan.
Use some tools to measure the pressure of systemˈ
YES
NO
YES
NO
Service diagnosis
Domestic air conditioner
Conditions
Supposed
Causes
Troubleshooting
Method of
malfunction detection
Malfunction detection
conditions