Safety Principles 
• During product maintenance, favorable ventilation shall be guaranteed at the maintenance site, and the close
of all the doors/windows is not allowed.
• Operation  with open fire  is  not  allowed, including  welding  and  smoking.  The  use  of  phones  is  also  not
allowed. The user shall be informed that cooking with open fire is not allowed.
• During maintenance in a dry season, when the relative humidity is less than 40%, anti-static measures shall
be taken, including the wearing of cotton clothes and cotton gloves.
• In case the leakage of flammable refrigerant is identified during maintenance, forced ventilation measures
shall be taken immediately, and the source of leak shall be plugged.
• In  case  the product  damaged  must  be  maintained  by  disassembling the  refrigeration  system,  the  product
must be delivered to the maintenance point. Welding of refrigerant pipelines at the user’s site is not allowed.
• During maintenance, in case re-treatment is required due to lack of fittings, the air conditioner shall be reset.
• The refrigeration system must be safely earthed in the whole course of maintenance.
• For the  door-to-door  service  with refrigerant cylinders, the  refrigerant charged inside  the cylinder cannot
exceed the specified value. The cylinder placed in vehicles or at the installation/maintenance site shall be fixed
perpendicularly and be kept away from heat sources, ignition source, source of radiation and electric appliance.
Maintenance Items 
Maintenance Requirements 
• Before the refrigeration system is operated, the circulating system shall be cleaned with nitrogen. Afterwards,
the outdoor unit shall be vacuumized, the duration of which cannot be less than 30 minutes. Finally, 1.5~2.0MPa
OFN  shall  be  used  for  nitrogen  flushing  (30  seconds~1  minute),  to  confirm  the  position  requiring  treatment.
Maintenance of the refrigeration system is only allowed after the residual gas of flammable refrigerant is removed.
• During the use of refrigerant charging tools, cross contamination of different refrigerants shall be avoided.
The total length (including the refrigerant pipelines) shall be shortened as much as possible, to reduce the residual
of refrigerant inside.
• The cylinders of refrigerant shall be kept upright, and be fixed.
• Before refrigerant charging, the refrigeration system shall be earthed.
• The refrigerant charged shall be of the type and volume specified on the nameplate. Excessive charging is
not allowed.
• After maintenance of the refrigeration system, the system shall be sealed with a safe manner.
• The maintenance in progress shall not damage or lower the original class of safety protection of the system.
Maintenance of Electrical Components 
• Partial of the electrical component under maintenance shall be subject to inspection on refrigerant leakage
with dedicated leak detection equipment.
• After the maintenance, the components with safety protection functions cannot be disassembled or removed.
• During  the  maintenance  of  sealing  elements,  before  opening  the  seal  cover,  the  air  conditioner  shall  be
powered  off  first.  When  power  supply  is  required,  continuous  leak  detection  shall  be  carried  out  at  the  most
dangerous position, to avoid potential risks.
• During  maintenance of  electrical components,  the  replacement  of  enclosures  shall not affect the  level  of
protection.
• After  maintenance,  it  shall  be  guaranteed  that  the  sealing  functions  will  not  be  damaged  or  the  sealing
materials  will  not  lose  the  function  of  preventing  the  entry  of  flammable  gas  due  to  aging.  The  substitute
components shall meet the recommended requirements of the air conditioner manufacturer.
Maintenance of Intrinsically Safe Elements 
The intrinsically safe element refers to the components working continuously inside flammable gas without any 
risks.
• Before any maintenance, leak detection and inspection on earthing reliability of the air conditioner must be
carried out, to ensure no leakage and reliable earthing.
• In case the allowable voltage and current limit may be surpassed during the service of the air conditioner,
any inductance or capacitance cannot be added in the circuit.
• Only the elements appointed by the air conditioner manufacturer can be used as the parts and components
replaced, or otherwise a fire may be triggered in case of refrigerant leakage.
• For the maintenance not involved in system pipelines, the system pipelines shall be well protected, to ensure
that no leakage will be caused due to maintenance.
• After maintenance and before test run, the air conditioner must be subject to leak detection and inspection on
earthing reliability with leak detection equipment or leak detecting solution. It shall be guaranteed that the startup
inspection is carried out without leakage and under reliable earthing.