180
Super Match
Drainage Test
(1) Conduct a drainage test after completion of the electrical work.
(2) During the trial, make sure that drain ows properly through the piping
and that no water leaks from connections.
(3) In case of a new building, conduct the test before it is furnished with the
ceiling.
(4) Be sure to conduct this test even when the unit is installed in the heating
season.
Procedures
(a) Supply about 1000 cc of water to the unit through the air outlet using a
feed water pump.
(b) Check the drain while cooling operation.
Before the electrical work has not been completed, connect a convex joint
in the drain pipe connection to provide a water inlet. Then, check if water
leaks from the piping system and that drain ows through the drain pipe
normally.
Installation work for air outlet ducts
Calculate the draft and external static pressure and select the
length, shape and blowout.
A. Blowout duct
2-spot, 3-spot and 4-spot with Ø200 type duct are the standard
specications.
Note
(1) Shield the central blowout hole for 2-spot.
(2) Shield the blowout hole around the center for 3-spot.
Limit the difference in length between spots at less than 2:1.
Reduce the length of duct as much as possible.
Reduce the number of bends as much as possible. (Corner R
should be as larger as possible.)
Use a band. etc. to connect the main unit and the blowout duct
ange.
Conduct the duct installation work before nishing the ceiling.
Connection of suction, exhaust ducts
a.Fresh air inlet
Inlet can be selected from the side or rear faces depending on
the working conditions.
Use the rear fresh air inlet when the simultaneous intake and
exhaust is conducted. (Side inlet cannot be used.)
b.Exhaust (Make sure to use also the suction.)
Use the side exhaust port.