Indoor Unit
181
Super Match
WARNING
Danger of bodily injury or death
Turn off electric power at circuit breaker or power source before making any electric connections.
Ground connections must be completed before making line voltage connection.
Precautions for electrical wiring
Electrical wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with
insulated grip on the ends of the wires.
Use copper conductor only.
Selection of size of power supply and interconnecting wires
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2%
voltage drop.)
Item
Model
Phase
Circuit breaker
Power source
wire size
(minimum)
(mm
2
)
Earth leakage breaker
Switch
breaker (A)
Over-current
protector rated
capacity (A)
Switch
breaker
(A)
Leak
current
(mA)
AD12MS1ERA AD12MS1ERA(D)
AD18MS1ERA AD18MS1ERA(D)
AD24MS1ERA AD24MS1ERA(D)
AD24MS2ERA AD24MS2ERA(D)
1 40 26 4.0 40 30
AD28MS2ERA(S) AD28MS2ERA(S)(D)
AD28NS1ERA(S) AD36NS1ERA(S)
AD48NS1ERA(S)
1 40 30 6.0 40 30
Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.
Outdoor unit
terminal block
1 2
3
Y/G
Power suppl
y
:1PH,220-230V~,50Hz
Outdoor unit
terminal block
1 2
3
Y/G
Power suppl
y
:380-400V, 3N~,50Hz
Indoor unit
1 2 3
Indoor unit
1 2 3
terminal block
Y/G
terminal block
Y/G
R S T N
L N
AD12MS1ERA AD12MS1ERA(D)
AD18MS1ERA AD18MS1ERA(D)
AD24MS1ERA AD24MS1ERA(D)
AD24MS2ERA AD24MS2ERA(D)
AD28MS2ERA(S) AD28MS2ERA(S)(D)
AD28NS1ERA(S) AD36NS1ERA(S)
AD48NS1ERA(S) (Outdoor single phase type)
AD48NS1ERA(S)(Outdoor 3 phase type)