Indoor Unit
183
Super Match
Before installation (Before nishing installation, do not throw the attached parts installation needs)
Conrm the way to move the unit to the installation place.
Before moving the unit to the installation place, do not remove their packages. When having to remove the
package, use a soft material or protection board with rope to lift the unit assembly to avoid unit damage or
bumping a scrape.
Choose installation place
The chosen installation place should meet the following requirements and get the user’s consent.
Place ensures ideal airow distribution.
The passage of airow has no obstacles.
When importing outside air, it should be imported directly from outdoors. (If the pipe can not be extended, it also
can not be imported from top)
Place ensures enough space for maintenance.
The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation
part).
The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television and radio. This
is to avoid the image disturbance and noise caused by the above mentioned home appliance. (Even if 1m away,
if the electromagnetic wave is too strong, it can also cause noise.)
The indoor unit can install on the ceiling, which height is no more than 3m.
Install and use the hoisting screw. check if the installation place can bear the weight of unit assembly. If not
certain, strengthen it before install the unit.
Installation for indoor unit
1. The position relation among hoisting screw (unit: mm)
2. If necessary, cut the opening installation and checking needed on the ceiling. (If having ceiling)
Before installation, nish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller
connection wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be
immediately connected with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and at and
prevent the ceiling from vibration. For details, please consult to the builder.