184
Super Match
3. Hanger bolts installation
Use care of the piping direction when the unit is installed.(Use M10
screw bolt)
In order to bear the weight of the unit, for existed ceiling, using
foundation screw bolt, and for new ceiling, using burying embedded
screw bolt, burying screw bolt or spot supplied other parts.
Before going on installation, adjust the gaps with ceiling.
4. Installation of indoor unit
Fix the indoor unit to the hanger bolts.
If required, it is possible to suspend the unit to the beam, etc. Directly by
use of the bolts without using the hanger bolts.
Note
When the dimensions of main unit and ceiling holes does not match, it
can be adjusted with the slot holes of hanging bracket.
5. Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method.
Make adjustment so that the relation between the lower surface of
the unit proper and water level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly,
Installation Procedure
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making
traps.