Outdoor Unit
315
Super Match
1.
Liquid Pipe φ9.52 X 0.8mm
Gas Pip φ15.88 X 1.0mm
1U24GS1ERA
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
and the bending radius should be 30 to 40
mm or longer.
Connecting the pipe of gas side rst makes working easier.
The connection pipe is specialized for R410A.
Connection of pipes
Piping size
2.
Half union
Flare nut
Torque wrench
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gas side 12.7mm(1/2") 55N.m
Gas side 15.88mm(5/8") 60 N.m
Be careful that matters, such as wastes of sand
s,water,
, etc. shall not enter the pipe.
CAUTION
The standard pipe length is C m. If it is over D m, the function of the unit will be affected. If the pipe
has
to be lengthened, the refrigerant should be charged,
according to E g/m. But the charge of refrigerant
must
be conducted by profes
sional air conditioner engineer. Before adding additional refrigerant,
perform
air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then
charge
additional refrigerant.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
Max.Elevation:
In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
In case the pipe length B is
more thanDm, the refrigerant
should be charged, according
to E g/m.
Amax
Bmax
Outdoor Unit Amax Bmax C D E
1U24GS1ERA 15 255 7 45
5.Refrigerant piping

Other manuals for Haier AB18CS1ERA