EasyManua.ls Logo

Haier AB18CS1ERA - Page 325

Haier AB18CS1ERA
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outdoor Unit
323
Super Match
1. Piping diagram for single split
1U24GS1ERA 1U28GS2ERA(S) 1U28HS1ERA(S)
1U36HS1ERA(S) 1U48LS1ERA(S) 1U48LS1ERB(S)
1U48LS1EAB(S)
1U48IS1EAB(S) 1U48IS1ERB(S) 1U60IS1ERA(S)
1U60IS1ERB(S) 1U60IS1EAB(S) 1U60IS2EAB(S)
1U60IS2ERB(S)
2. Piping size for single split
1U24GS1ERA 1U28GS2ERA(S)
1U28HS1ERA(S) 1U36HS1ERA(S)
Liquid pipe Ф9.52×0.8mm
Gas pipe Ф15.88×1.0mm
1U48LS1ERA(S) 1U48LS1ERB(S)
1U48LS1EAB(S) 1U48IS1EAB(S)
1U48IS1ERB(S) 1U60IS1ERA(S)
1U60IS1ERB(S) 1U60IS1EAB(S)
1U60IS2EAB(S) 1U60IS2ERB(S)
Liquid pipe Ф9.52×0.8mm
Gas pipe Ф19.05×1.0mm
Install the removed are nuts to the pipes
to be connected, then are the pipes.
3. Limitations for one way piping length and vertical height difference for single split
Model One way piping length
Vertical height difference
(between indoor and outdoor)
1U24GS1ERA 1U28GS2ERA(S)
1U28HS1ERA(S) 1U36HS1ERA(S)
less than 30 m less than 20 m
1U48LS1ERA(S) 1U48LS1ERB(S) 1U48LS1EAB(S)
1U48IS1EAB(S) 1U48IS1ERB(S) 1U60IS1ERA(S)
1U60IS1ERB(S) 1U60IS1EAB(S) 1U60IS2EAB(S)
1U60IS2ERB(S)
less than 50 m less than 30 m
Precautions for refrigerant piping
Do not twist or crush piping.
Be sure that no dust is mixed in piping.
Bend piping with as wide angle as possible.
Keep insulating both gas and liquid piping.
Check are-connected area for gas leakage.
4 Piping connection method
Apply refrigerant oil to the joint and the ange.
To bend a pipe, give the roundness as possible not
to crush the pipe.
When connecting pipe, hold the pipe centre to
centre and then screw nut on by hand, refer to Fig.
Be careful not to let foreign matters, such as sands
enter the pipe.
Pipe diameter Fastening torque (N.m)
Liquid pipe Ф6.35mm 14.2-17.2
Liquid pipe Ф9.52mm 32.7-39.9
Gas pipe Ф12.7mm 49.5-60.3
Gas pipe Ф15.88mm 61.8-75.4
Gas pipe Ф19.05mm 97.2-118.6
Forced fastening without centering may damage the threads and cause a gas leakage.
5. For the allowable pipe length and height difference for maxi split system, please see the table in the page
2 of this manual.

Other manuals for Haier AB18CS1ERA

Related product manuals