336
Super Match
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve caps from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After ve to ten minutes, close the liquid stop valve with a
hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop
forced cooling operation.
wernch
Wiring work
1. Electric wiring
■ The air conditioner must use special circuit , and wiring by the qualied electrician according to the wiring rules
specied in national standard.
■ The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire
is incorrect. The electric leakage breaker must be installed.
■ All the electric wire must be copper wire.Power supply: 1PH, 220-230V~, 50Hz.
■ The wiring method of power line is Y connection. If the power line is damaged, in order to avoid risk of electric
shock, it must be replaced by the manufacturer or its repair center or other similar qualied person.The
connecting cable must be shielded.
Fuse: T3.15A 250VAC(Electronic control unit) T25A 250VAC(Power circuit board). Please check the circuit
diagram about the fuse replaced.
2. Wiring method
■ Wiring method of orbicular terminals
For the connection wire with orbicular terminals, its wiring method is as shown in the right
gure: remove the connecting screw, put the screw through the ring on the end of the
wire, then connect to the terminal block and fasten screw.
Wiring method of straight terminals.
■ For the connection wire without orbicular terminals, its wiring
method is: loosen the connection screw, and insert the end of the
connection wire completely into the Terminal block, then fasten the
screw.
Slightly pull the wire outwards to conrm it is rmly held.
■ Crimp connection method for wires without terminals
Wiring Method for Ring
Terminal Block
Pressing
clamps
■ Crimp connection method for connection wire
After connection,the wire must be fastened by wire cover. The wire cover shall press on the protection coat of the
connection wire,as shown in right top gure.
Note:
When connecting the wiring,conrm the terminal number of indoor and outdoor units carefully. Incorrect wiring will
damage the controller of air conditioner or the unit can not operate.