360
Super Match
Dip switch setting
PCB 0151800054A dip switch setting
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
OFF OFF --- --- --- --- --- --- 28K outdoor unit
OFF ON --- --- --- --- --- --- 36K outdoor unit
ON OFF --- --- --- --- --- --- 48K outdoor unit+1U60IS2ERB(S)
ON ON --- --- --- --- --- ---
60K outdoor unit(except
1U60IS2ERB(S))
--- --- OFF --- --- --- --- --- Power module choose 1
--- --- ON --- --- --- --- --- Power module choose 2
--- --- --- OFF --- --- --- --- DC fan motor
--- --- --- ON --- --- --- --- AC fan motor
--- --- --- --- OFF --- --- --- Double fan
--- --- --- --- ON --- --- --- Single fan
--- --- --- --- --- OFF --- --- Old comunication protocol
--- --- --- --- --- ON --- --- New communication protocol
--- --- --- --- --- --- OFF --- 3 phase
--- --- --- --- --- --- ON --- 1 phase
--- --- --- --- --- --- --- OFF Without quiet mode(default)
--- --- --- --- --- --- --- ON With quiet mode
SW6-1 SW6-2 SW6-3 SW6-4 Discription
OFF --- --- --- Non-rated operation(default)
ON --- --- --- Rated operation
--- OFF --- --- Normal defrosting(default)
--- ON --- --- Compulsory defrosting
--- --- OFF --- Normal cooling(default)
--- --- ON --- Compulsory cooling
--- --- --- OFF Normal heating(default)
--- --- --- ON Compulsory heating
PCB 0151800129A dip switch setting
1 2 3 4 5 6 7 8 Decription
ON OFF --- --- --- --- --- --- 48K outdoor unit
ON ON --- --- --- --- --- --- 60K outdoor unit
--- --- OFF --- --- --- --- without sunction sensor
--- --- ON --- --- --- --- With sunction sensor(default)
--- --- --- OFF --- --- --- --- Double fan
--- --- --- ON --- --- --- --- Sinlge fan
--- --- --- --- OFF --- --- --- 1 phase
--- --- --- --- ON --- --- --- 3 phase(default)
--- --- --- --- --- OFF --- --- Without high pressure detecting
--- --- --- --- --- ON --- --- With high pressure detecting
--- --- --- --- --- --- OFF --- With low current detecting
--- --- --- --- --- --- ON --- Without low current detecting(default)
--- --- --- --- --- --- --- OFF inquiry failure (outdoor ambient 10K)
--- --- --- --- --- --- --- ON inquiry failure (outdoor ambient 23K)