EasyManua.ls Logo

Haier AB25S2SC1FA - Page 53

Haier AB25S2SC1FA
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
Item Model 4U85S2SH1FA
Piping
Refrigerant
Type / Charge kg R32 / 2.5
GWP 675
No need to recharge m 40
Recharge g/m 20
Pipe
Liquid mm 4* Φ6.35
Gas mm 3* Φ9.52+1*Φ12.7
Connecting method - Flared
Between
I.D &O.D
Drop between IU & OU m ≤7.5
Piping length between IU & OU m ≤10
Total liquid piping length m ≤40
Drop between indoor units m ≤1
Max.Drop between IU &OU m 15
Max.Drop between indoor units m 7.5
Max.Piping length between IU & OU m 25
Max Cable length between IU & OU m 30
Max.Total length m 70
Working temperature
Cooling °C -10~46
Heating °C -15~24
Tdisignh: -10°C Tbivalent: -7°C TOL: -15°C
Pto: 60W Psb: 12W Pck: 0W Poff: 0W
Cooling
A (Cap/EER) 8360W/3.54
Heating
A (Cap/COP) 6535W/2.81 Tol (Cap/COP) 5973W/2.32
B (Cap/EER) 5806W/5.98 B (Cap/COP) 4030W/4.10 Tb (Cap/COP) 6535W/2.81
C (Cap/EER) 3767W/8.47 C (Cap/COP) 2462W/4.98 Cd (cooling) 0.25
D (Cap/EER) 3786W/10.73 D (Cap/COP) 2840W/6.24 Cd (heating) 0.25
Max. cooling condition
Indoor
temperature:
32°C/23°C
Max. heating condition
Indoor temperature: 27°C/-°C
Outdoor
temperature:
46°C/-°C
Outdoor temperature: 24°C/18°C
kWh/annum 454 kWh/annum-average 2442
kWh/annum-
warm
1192
1. The above performance data are from the combination of 4U85S2SH1FA+3*AS25S2SN1FA+1*AS35S2SN1FA.
2. Large drop and long piping installation will obviously reduce the total capacity.

Other manuals for Haier AB25S2SC1FA

Related product manuals