>a__WcU[S^ <[c >a`V[e[a`Wc
11.2 For wall mounted type and the console type unit, their failure code is below:
Failure description
Code on wired
controller
(YR-E06)
Flash times of indoor receiver
board
Room temp. sensor abnormal
F1 Power LED flashes 1 time
Indoor coil temp. sensor abnormal (liquid pipe)
F2 Power LED flashes 2 times
Refrigerant system abnormal
F3 Power LED flashes 3 times
Indoor coil temp. sensor abnormal (gas pipe)
F4 Power LED flashes 4 times
High pressure abnormal (outdoor)
F5 Power LED flashes 5 times
Drainage abnormal
F6 Power LED flashes 6 times
Communication between indoor and wired controller
F7 Power LED flashes 7 times
Indoor fan motor abnormal (up)
Power LED flashes 8 times
Indoor fan motor abnormal (down)
Power LED flashes 9 times
3 phase abnormal
E1 Running LED flashes once
Low pressure abnormal (outdoor) E2 Running LED flashes twice
Communication between indoor and outdoor abnormal
E3 Running LED flashes 3 times
Compressor overheat E4 Running LED flashes 4 times
CT current abnormal E5 Running LED flashes 5 times
Outdoor ambient temp. sensor abnormal
E6 Running LED flashes 6 times
Outdoor coil pipe temp. sensor abnormal
E7 Running LED flashes 7 times
Outdoor suction temp. sensor abnormal
EA Running LED flashes 10 times
A
bnormal modes running
EC Running LED flashes 11 times
Outdoor discharging temp. sensor abnormal
ED Running LED flashes 12 times
Indoor EEPROM abnormal EE Running LED flashes 14 times
Note: Resumable failures are marked with “ ”, the others are not resumable failures.
Resumable failure will disappear when the failure is eliminated and its failure code will
disappear automatically within 30 seconds. But the other failure code will disappear only
after the unit starts up once again.