Indoor Unit
123
Super Match
Item Model AD24MS2ERA/1U24GS1ERA
Function cooling heating
Capacity KW 7.1(2.0~8.2) 8.0(2.5~8.5)
Sensible heat ratio 0.74 /
Total power input KW 2.19(0.6~2.6) 2.16(0.6~2.6)
Max. power input W
2600 2600
EER or COP W/W 3.23 3.71
Dehumidifying capacity 10
-
³×m³/h 2.5
Power cable H05RN-F 4G 6.0mm
2
Power source N, V, Hz
1PH, 220-230V~, 50/60Hz
Running /Max.Running current A / A 10.5(2.3-12)/12 9.2(2.3-12)/12
Start Current A 3
Indoor unit
Unit model (color) AD24MS2ERA
Fan
Type × Number CENTRIFUGALX2
Speed(H-M-L) r/min 950/860/760
Fan motor output/ input power W 85/111
Air-ow(H-M-L) m³/h 1050/840/630
External static pressure Pa 10/30(default)/50/70
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Row 3
Total Area 7.668
Dimension
External(L×W×H) mm×mm×mm 957/655/250
Package(L×W×H) mm×mm×mm 1170/860/340
Drainage pipe (material , I.D./O.D.) mm PVC 25/29
Controller
(O-Optional,S-Standard)
Wired YR-E16(O)/YR-E17(S)
Fresh air hole dimension mm NONE
Electricity Heater kW NONE
Sound power Noise level (H-M-L) dB(A) 58
Sound pressure Noise level (H-M-L) dB(A) 42/38/35
Pipe
Liquid Pipe(mm) 9.52
Gas Pipe(mm) 15.88
Connecting Method ared
Weight (Net / Shipping) kg / kg 31.2/36.8
cooling Pdesignc(kW): 7.1KW SEER/CLASS 6.1/A QCE(Annual electricity consumption for cooling)kWh: 415
heating
Average Pdesignh(-10
o
C) 6.0KW SCOP/CLASS 4.0/A QHE(Annual electricity consumption for heating)kWh: 2103
Warmer Pdesignh(2
o
C) 6.5KW SCOP/CLASS 4.8/A++ QHE(Annual electricity consumption for heating)kWh: 1895
Colder Pdesignh(-22
o
C) / SCOP/CLASS / QHE(Annual electricity consumption for heating)kWh: /
Tdesignh
-10
Tbivalent:-8
o
C TOL:-15
o
C Elbu:0
Max. cooling
condition
Indoor temperature
32
/23
Max. heating condition
Indoor temperature:27
o
C/-
o
C
Outdoor temperature
46
/-
Outdoor temperature:24
o
C/18
o
C
Norminal condition: indoor temperature (cooling): 27
o
CDB/19
o
CWB, indoor temperature (heating): 20
o
CDB
Outdoor temperature(cooling): 35
o
CDB/24
o
CWB, outdoor temperature(heating): 7
o
CDB/6
o
CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a