226
Super Match
Item Model 1U48LS1ERA(S)
Power cable H05RN-F 3G 6.0mm2
connecting cable(including communication cable) H05RN-F 4G 2.5mm2
Power source N, V, Hz 1PH, 220-230V~, 50Hz
Start Current A _
Outdoor
unit
Unit model (color) 1U48LS1ERA(S)
WHITE
Compressor
Model / Manufacture/place
TNB306FPGMC/MITSUBISHI ELECTRIC
CORPORATION
Oil model PVE
FV50S
Oil charging 870CM3
Type Rotary 1
Fan
Type × Number axial×1
Speed r/min High 840
Fan motor input power kW /
Fan motor output power kW 0.151
Air-ow(H-M-L) m³/h 4200
Heat exchanger
Type / Diameter mm TP2M/Φ7.94
Row/Fin pitch 2 1.4
Total area
Dimension
External
L×W×H
mm×mm×mm 1008×447×830
Package
L×W×H
mm×mm×mm 1130×490×930
Drainage pipe (material , I.D./O.D.) mm none
Refrigerant control method mm/mm ELECTRONIC VAVE 2.4MM
Defrosting auto
Volume of Accumulator L 3.4
Sound power Noise level(H-M-L) dB(A) 73
Sound pressure Noise level (H-M-L)
dB(A) 59
Type of four way valve SHF-20A-46
material of reduce noise XPE
crankcase heater power W 38
Weight(Net / Shipping) kg / kg 82/93
Piping
Refrigerant
Type / Charge g R410A/2850
Maximum pipe length
without recharge refrigerant
m 20
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Connecting Method ared
Between I.D
&O.D
MAX.Drop m 30
MAX.Piping length m 50
Working
temp
Cooling (Min-Max)
O
C -10~46
Heatling (Min-Max)
O
C -15~24
Norminal condition: indoor temperature (cooling): 27
DB/19
WB, indoor temperature (heating): 20
DB
Outdoor temperature(cooling): 35
DB/24
WB, outdoor temperature(heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter. It is a sound pressure noise level.