Outdoor Unit
227
Super Match
Item Model 1U48LS1ERB(S)
Power cable H05RN-F 4G 4.0mm
2
Connecting cable
(including communication table)
H05RN-F 4G 2.5mm
2
Power source N, V, Hz 3N~,380
~
400, 50
Start Current A 5
Outdoor
unit
Unit model (color) 1IU48LS1ERB(S)
(
WHITE
)
Compressor
Model / Manufacture/
place
TNB306FPNMC/MITSUBISHI
ELECTRIC CORPORATION
Oil model PVE
(
FV50S
)
Oil charging 870CC
Type Twin Rotary
Fan
Type × Number axial×1
Speed r/min 850±50/650±50/500±50
Fan motor input power kW 0.225×1
Fan motor output power kW 0.145×1
Air-ow(H-M-L) m³/h 4200/3500/2500
Heat
exchanger
Type / Diameter mm TP2M/Φ7.94
Row/Fin pitch 2
1.4
Total area m² /
Dimension
External
(
L×W×H
)
mm×mm×mm 1008×447×830
Package
(
L×W×H
)
mm×mm×mm 1142×498×1000
Drainage pipe (material , I.D./O.D.) mm none
Refrigerant control method mm/mm ELECTRONIC VAVE 2.4MM
Defrosting auto
Volume of Accumulator L 3.4
Sound power Noise level (H-M-L) dB(A) 73
Sound pressure Noise level (H-M-L) 59
Type of four way valve SHF-20D-46
material of reduce noise XPE
crankcase heater power W 38
Weight(Net / Shipping) kg / kg 82/93
Piping
Refrigerant
Type / Charge g R410A/2850
Maximum pipe length
without recharge
refrigerant
m 20
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Connecting Method ared
Between I.D
&O.D
MAX.Drop m 30
MAX.Piping length m 50
Working temp
Cooling (Min-Max)
O
C 10~46
Heatling (Min-Max)
O
C -15~24
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It
is a sound pressure noise level.