Outdoor Unit
229
Super Match
Item Model 1U60IS1ERB(S)
Power cable H05RN-F 5G 2.5mm2
Connecting cable(including communication cable) H05RN-F 4G 2.5mm
2
Power source N, V, Hz 3N~,380
400, 50/60Hz
Start Current A 5
Outdoor
unit
Unit model (color) 1U60IS1ERB(S)
WHITE
Compressor
Model / Manufacture/place
LNB42FUAMC(MITSUBISHI ELECTRIC COMPRESSOR
CO.,LTD
Oil model FV50S
Oil charging 1400CC
Type Twin Rotary
Fan
Type × Number axial×2
Speed r/min 930±40
Fan motor input power kW 0.125×2
Fan motor output power kW 0.10×2
Air-ow(H-M-L) m³/h 6500
Heat exchanger
Type / Diameter mm TP2M/Φ7.94
Row/Fin pitch 2 1.5
Total area 1.17
Dimension
External
L×W×H
mm×mm×mm 948×340×1250
Package
L×W×H
mm×mm×mm 1095×410×1400
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm Electronic Expansion Valve 3.0mm
Defrosting auto
Volume of Accumulator L 4.0
Noise level dB(A) 60
Type of four way valve SHF-20D-46
material of reduce noise XPE
crankcase heater power W 38
Weight(Net / Shipping) kg / kg 96/106
Piping
Refrigerant
Type / Charge g R410A/3300
Maximum pipe length without
recharge refrigerant
m 20
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Connecting Method ared
Between I.D
&O.D
MAX.Drop m 30
MAX.Piping length m 50
Working temp
Cooling (Min-Max)
O
C -10~46
Heatling (Min-Max)
O
C -15~24
Norminal condition: indoor temperature (cooling): 27
DB/19
WB, indoor temperature (heating): 20
DB
Outdoor temperature(cooling): 35
DB/24
WB, outdoor temperature(heating): 7
DB/6
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It is a
sound pressure noise level.