107
Item Model
3U55S2SR2FA
Function - Cooling Heating
Rating Capacity W 5500 6800
Cooling Pdesign W 5500
Heating Pdesign (-10°C) W 4700
Rated Power Input (Indoor + Outdoor) W 1380 1550
Rated Current Input (Indoor + Outdoor) A 6.4 7.1
EER/COP W/W 4.0 4.4
SEER/SCOP W/W 7.5 4.0
Minimum Capacity W 2100 1700
Minimum Power Input W 550 550
Maximum Capacity W 7000 7600
Maximum Power Input (Indoor + Outdoor) W 2500 2200
Power Source - 1PH, 220-240V~, 50/60Hz
Max. Running Current (Indoor + Outdoor) A/A 10.8 9.5
Power Facor (Under Rating Power Input) - 99% 99%
Starting Current A 4
Fuse Size (Recommended Size) A 25
Outdoor Unit
Compressor
Model / Manufacture - SVB140FCAMC-L/ MELCOM
Oil Charge and Type - 500CC/ FW68S
Type - Twin Rotary (DC Inverter)
Number - 1
Fan
Type × Number - Axial × 1
Speed r/min High 700
Motor Output/Input Power W 90/130
Air-Flows (H/M/L) m³/h About 3000
Heat Exchanger
Type / Diameter mm TP2M / 9.52
Row - 1
Face Area About 0.6
Dimension
(WxDxH)
External mm 890/340/700
Package mm 998/443/770
Refrigerant Control Method - EEV
Defrosting Method - Automatic By Reversible Cycle
Crankcase Heater Power W None
Noise Level
Sound Power Level dB(A) 64
Sound Pressure Level dB(A) 51
Weight Net/Shipping kg / kg 51/55