271
236
yes
[43-0, 43-1] protection of discharging temperature too low
no
no
no
yes
yes
no
check indoor electronic
expansion valve
re-connect the terminals
yes
in heating mode, check
if terminal of LEVb is
fixed well, if it leaks
in heating mode, check
terminals of LEVb, LEV A1,
LEV A2 are connected
respectively
check if refrigerant is too
much
if Toil is fixed well and
if its characteristic is correct
check LEVb
recharge refrigerant
in cooling mode, check
if electronic expansion valve
of indoor unit which is not
running does not
close fully
fix again or replace the sensor