Commercial Air Conditioner Model: AU96NATAEA
AD96NAHAEA, AP96NACAEA
62
if the power LED on indoor PCB is
proper
yes
yes
yes
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
check if there is
voltage output at
the fan motor output
terminal
check if power supply is proper
check if the fuse is proper
check if the voltage dependent
resistor is conductive
change
fuse
check if there
is level output
at the chip of
PCB
check if the fan
capacitor is proper
check if fan
speed control
relay is bad
change voltage
dependent resistor
if the chip of
PCB is bad
check if fan motor
coil is proper
change fan
capacitor
change voltage
dependent resistor
change PCB
change fan
motor
Figure 3
b. Outdoor fan not running
 
change
fuse
no
yes
check if there is
voltage output at
the fan motor output
terminal
no
check if power supply is proper
yes
check if the fuse is proper
yes
check if the voltage dependent
resistor is conductive
check if fan
speed control
relay is bad
yes
check if there
is level output
at the chip of
PCB
yes
no
no
check if the fan
capacitor is proper
yes
no
check if fan motor
coil is proper
change fan
capacitor
if the chip of
PCB is bad
yes
yes
no
change fan
motor
change PCB
change voltage
dependent resistor
if the power LED on outdoor PCB
is proper
change voltage
dependent resistor
yes
Figure 4
10.2 Failure code
AP96NACAEA adopts operation panel+infrared control type, while AD96NAHAEA adopts wired
control type. If the air conditioner occurs failure, the failure code will be displayed on the wired
controller or the operation panel as the following chart:
Failure code Reason
E0 Indoor float switch abnormal
E1 Indoor ambient temp. sensor abnormal