146
Smart Power
7.9.2 Connecting power supply and inter-unit wiring
• Connect and x the power supply cable, indoor-outdoor connection cable as following:
For three phase power supply models:1UH125P1ERK,1UH140P1ERK,1UH200W1ERK,1UH250W1ERK,
Power supply cable:
For 1UH125/140P1ERK H05RN-F 5G 2.5mm
2
For1UH200/250W1ERK H05RN-F 5G 4.0mm
2
Indoor and outdoor connection cable:
H05RN-F 4G 2.5mm
2
Y?
Y?
Y?
Y?
For single phase power supply models:1UH071N1ERG,1UH090N1ERG,1UH105N1ERG, Power supply cable:
H05RN-F 3G 4.0mm
2
1UH125P1ERG,1UH140P1ERG,1UH160P1ERG
Power supply cable: H05RN-F 3G 6.0mm
2
Indoor and outdoor connection cable: H05RN-F 4G 2.5mm
2

Other manuals for Haier ADH200H1ERG