Domestic Air Conditioner
26
When Tpg_indoor begins to rise again, and ice_temp_2İTpg_indoorİice_temp_3ć, the frequency
of thecompressor doesn’t change.
When ice_temp_3LJTpg_indoorLJice_temp_3+3ć, the frequency of the compressor increases at the
speed of 1HZ/10seconds.
For example, Tpg_indoorİ0ćˈlast for 2 minutes, and then the outdoor unit will stop, and report
underload malfunction, but don’t send malfunction report to the indoor.
The compressor stops for more than 3 minutes, Tpg_indoor> ice_temp_3+2ć, the compressor
recovers.
5.2.5.6 The frequency limitation of modification rate
In the field which is controlled by high frequency, if the modification rate is not high enough, the
control-driven chip will enter into weak magnetic control, this will help to relieve the problem of
modification rate. If during the course of weak magnetic control, the modification rate is still not high
enough, enter into the control of decreasing frequency until the alarm of modification rate is relieved.
5.2.5.7 Temperature protection of the outdoor refrigerating coil
When the defrosting temperature and the sensor’s temperature are higher than 68ć, the frequency of
the compressor decreases 1hz/10seconds. Keep the frequency until it decreases to the lowest
frequency. When the temperatures are lower than 68ćand higher than 61ć, keep the frequency of
the compressor. When the temperatures are lower than 61ć, relieve the defrosting temperature
protection.
5.2.5.8˖Malfunction display and malfunction handling
a)ǃFor the complete appliance’s malfunctions˖Annex 2
If there’s malfunction with the outdoor unit, the light of the outdoor unit will flash and its frequency is
1HZ, the number of times is according to the table, when a round of flashing is finished, the light
shoud be off for 5 seconds.
b)ǃFor the units’ malfunctins˖Annex 1
If there’s malfunction with the units, this will not affect the run of the complete appliance, but this can
be displayed by the malfunction light, the light flashing frequency is 0.5HZ, the number of times is
according to the malfunction table of the indoor units. When a round of flashing is finished, the light
shoud be off for 10 seconds. Then report according to the order : unit Aėunit Bėunit Cėunit D, that
is, if there’s malfunction with several units, then just report the indoor unit with the highest priority level.
Among the unit malfunctions, the priority level of the communication malfunction is the highest, for
others, that appears first will have the priority.
Remarks: in 3 minutes when the compressor stops, the units’ malfunctions are not displayed; the
complete appliance’s malfunctions are prior to the units malfunctions.
Annex 1˖Malfunction codes of the whole unit
Remarks: under the mode of refrigeration, the malfunctions of each unit’s thin pipe temperature
sensor are not reported, under the mode of heating, the malfunctions of each unit’s thick pipe
temperature sensor are not reported.
Funcitions and Control