AS24GS1/2ERA 1U24GS1ERA-SM Service Diagnosis
Domestic Air Conditioner
65
7.4.2 Indoor fan motor malfunction
W)B((-/=C.L4EJ/
S#N
8*,A(B/(K/ / / / / / / /
The rotation speed detected by the Hall IC during fan motor operation is used to determine
8E4KG)+,C()/ /////
abnormal fan motor operation
/
=*,*+,C()/
8E4KG)+,C()/ ////
when the detected rotation feedback singal don’t receiced in 2 minutes
/
=*+C.C()//// /
"()BC,C()./
&GLL(.*B// "EG.*./
Ƶ
/
Operation halt due to breaking of wire inside the fan motor .
Ƶ
Operation halt due to breaking of the fan motor lead wires
Ƶ
/
Detection error due to faulty indoor unit PCB
/
6(R/,(/+A*+V/5E)/8(,(-/2="3
1. Check connector connection.
2. Check motor power supply voltage output (pins 1-4).
3. Check motor control voltage (pins 4-5).
4. Check rotation command voltage output (pins 4-6).
5. Check rotation pulse input (pins 4-7).
Notes:the a/c is electrifying,don’t pull out or insert the terminals of the
motor,else the motor would be damaged
Troubleshooting
&DXWLRQ
Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.