1U07BS1ERA
1U09BS1ERA
1U12BS1ERA
1U18FS1ERA
1U24GS1ERA
1.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
ƽ
and the bending radius should be 30 to 40
mm or longer.
Connecting the pipe of gas side first makes working easier.
ƽ
The connection pipe is specialized for R410A.ƽ
Half union
Flare nut
Torque wrench
CAUTION
Be careful that matters, such as wastes of sand
s,water,
, etc. shall not enter the pipe.
The standard pipe length is C m. If it is over D m, the function of the unit will be affected. If the pipe
has
to be lengthened, the refrigerant should be charged,
according to E g/m. But the charge of refrigerant
must
be conducted by profes
sional air conditioner engineer. Before adding additional refrigerant,
perform
air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gas side 12.7mm(1/2") 55N.m
Gas side 15.88mm(5/8") 60 N.m
Max.Elevation:
●
In case the elevation A is more
●
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
●
In case the pipe length B is●
more thanDm, the refrigerant
should be charged, according
to E g/m.
Connection of pipes
charge
additional refrigerant.
Amax
Bmax
2.
AS24GS1/2ERA 1U24GS1ERA-SM
87
Domestic air conditioner
Installation