Remove air intake screen and take out the front wires.
Connect the wires as specified in the above
methods and diagrams for indoor unit and wire con-
nections.
Properly apply capping clips on the wires.
Replace the air intake screen.
Do not link the connecting and signal wire with the
same cable, a snug space must be maintained
between connecting and signal wires.
Shield of the signal wire should be spot grounded.
Incorrect address setting will cause abnormal to the system.
Communication cable must be use sheilded type.
Incorrect address setting will cause abnormal to the system.and then put it down
perpendicularly.
Signal connecting cable must be sheilded type.
The distance between the signal wires and the power cabes should be at least 50mm.
WARNING
Correct crimp
connection of wire
Incorrect crimp
connection of wire
1(L) 2(N)
P
Q
1(L) 2(N)
P
Q
1(L) 2(N)
P
Q
TO OUTDOOR UNIT
L N
C1 C2
(P) (Q)
Communication cable (Shield
wire): H05RN-F 2X1.5mm
2
Power cable : H05RN-F 3G 2.5mm
2
Wiring connection:
Wiring of indoor unit
Block terminal
Capping clip
Wiring diagram of loop terminals
-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
78-