Before test run
Make sure if the resistor between terminal row (Terminal L, N) of power supply and grounding point is over 1M*
by using mega-ohmmeter (500v) before switch on.
If less than 1M* , operation cannot be executed.
Switch on outdoor unit. Electrify the shell body of the compressor. In order to protect the compressor, electrify 12
hours before operation.
It is strictly forbidden to oblige test run with canceling protecting device by hands.
(Because no work of protect device is very dangerous)
Method of test run
Method of installation and trial run
SW01 SW02
5
6
7
8
0
1
2
4
9
13
14
15
0
Display of numeral pipe light with seven segments
Checking code of outdoor unit Display: --- When no checking code
When total capacity of indoor units exceeds 130% of rated capacity of outdoor unit, display: F F F
Operation mode of outdoor units: Cooling: -C, Heating: -H , Defrosting: -J
Corrected value of defrosting temperature:display 1---denote L value is 12;
display 2---denote L value is 10;
display 3---denote L value is 8;
Target of operating frequency of compressor (Decimal number):
Actual operating frequency of compressor (Decimal number):
Indoor units connected (Decimal number):
Sensor backup operating: Sensor TS: 1-, Sensor TE: -1
Sensor backup operating: Sensor PD: 1-, Sensor PS: -1
Sensor backup operating: Sensor TA: 1-, Sensor TC: -1
Corrected value of compressor capacity: Level 4: 0, Level 6: 1
Permission setting of capacity over loading: Permitting: U Not permitting over: d
Format of communicating code: Format1: 01, Format2: H1
Others and Test Run
1. Marks for connecting units
When install multi-air condition system, in order to make clear of the connecting relation between outdoor unit and
each indoor unit, make a table on cover of electric box to indicate names of each indoor unit connected. (As follow)
2. Test run
When running test, please refer to instructions of operation and performance simultaneous.
In case of failing to start up in common way because of room temperature, test run can be executed through outdoor
unit.
1. Function explanation of switch SW01, SW02 of control panel of outdoor unit.
We can know the number of some parameters by using forck board ,but must to connected other frock borad.
which is not in the control board.The forck board must be bought from manufacturer.