13. Position of switches before delivery
Number of SW
Function Content of function
Position when delivery
SW01
Number setting
of indoor unit
Setting in group running control
0: master unit 1~15: slave unit
SW02
Address setting of
central control
No.7: ON, remote controller can not set address
No.7: OFF, remote controller can set address
For content of address setting, refer to the
following page
SW03
No.1,2 Temperature
compensation of
room temperature
control
Temperature compensation of room temperature
when heat running
No.1/2 ON/ON ON/OFF OFF/ON
OFF/OFF
Control
temperature
+0* +2* +4* +6*
No.3
Not used
No.3 In the state of OFF
SW04
Setting of emergency
running
ON emergency running
OFF Normal running
SW05
Setting of indoor HP
Have been set before delivery
For content of setting, refer to the
following page
SW06
Airflow rate
compensation
(only for cassette)
When installing height exceeds 2.7 m,
No.1, No.2 setting is on the ON side
No.3 not used
SW07
After running for 29 minutes, change into
rated power running
No.1: ON
No.1: OFF
usual
No.2: OFF
Heat pump
No.2: ON Cooling only