17. Back up running
a. Indoor unit
When the sensor of indoor unit have fault as shown in Table 1, it will automatically enter into back up runningwhile displaying the inspection code. During back up running, the capacity modification control can not beconducted. So the unbalance of capacity will occur. Therefore, the fault sensor must be replaced. When thefault other than that shown in Table 1 occur, such as TC1 x 2 + pressure, TC2 + Pressure, TC1 x 2 + TC2 +TA, etc. Because the reliability has problem, so the indoor unit with fault should be closed. When the indoor unit is under back up running, if the outdoor unit is in manual back up running, the compressormay have fault. So this should be strictly forbidden.
Table 1
Sensor with fault Treatment Inspection code
TC1 Conduct normal control by using another TC sensor
TC2
Automatic back up running
94
Pressure Automatic back up running
B9
TA Automatic back up running 0C
TC1 x 2 Automatic back up running
93
TC2 +TA Automatic back up running 94, 0C
Pressure + TA Automatic back up running B9, 0C
TC1 x 2 + TA
Automatic back up running
93, 0C
b. Outdoor unit
The sensor used by outdoor unit can be classified as automatic back up running and manual setting back uprunning. (refer to the following page)
Sensor Treatment Inspection code
Pd (discharge pressure)
Manual back up running (Fixed on Pd =1.96 Mpa (20kgf/cm2)
Ps ( intake pressure)
Manual back up running (Fixed on Ps =0.392 Mpa (4kgf/cm2)
TS ( intake temperature)
Manual back up running (TS = 10*)
TE (Heat exchanger
temperature)
A2
Manual back up running (Fixed on TE = 20 *)
18