Haier AU96NFTAHA - (2) Back up running method of outdoor unit; 1. Inverter running (6 HP outdoor unit does not have this function); 2. Back up running of commercial compressor; 3. Back up running of Pd sensor

Haier AU96NFTAHA
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Back up running of Ps sensor When the Ps sensor has fault, conduct running by fixing the value (4kgf/cm2) of Ps sensor.
3. Back up running of Pd sensor
When the Pd sensor has fault, conduct running by fixing the value (20kgf/cm2)
of Pd sensor.
(1)Cut off the main power supply;
(2)Turn the first digit on the outdoor unit I/F PCB to ON state;
(3)Switch on the main power supply, conduct normal trial run;
117
SW03
ON
1 2 3
SW03
ON
1 2 3
SW06
ON
1 2 3
SW06
ON
1 2 3
(2) Back up running method of outdoor unit
1. Inverter running (6 HP outdoor unit does not have this function) When the inverter circuit or the inverter compressor has fault, only the commercialcompressor runs.
(1)Cut off the main power supply;
(2)Turn the first digit of SW03 on the outdoor unit I/F PCB to ON state;
(3)Switch on the main power supply, conduct normal trial run;
(4)Make total running amount of indoor unit up to over 5 HP.
2. Back up running of commercial compressor
(HP outdoor unit does not have this function)
When the Mg-SW for fixed commercial or commercial compressor has
fault, only the inverter compressor runs.
(1)Cut off the main power supply; (2)Turn the second digit of digit 3 on the outdoor unit I/F PCB to ON state; (3)Switch on the main power supply, conduct normal trial run;
(1)Cut off the main power supply;
(2)Turn the second digit on the outdoor unit I/F PCB to ON state;
(3)Switch on the main power supply, conduct normal trial run;
In the following conditions, running is strictly forbidden:1)Outdoor heating running below 7*;2)Low pressure running caused by recovering refrigerant.
5. Back up running of TS sensor
When the TS sensor has fault, it will automatically enter into back up running by fixing the value (10*) of
TS sensor. The SW01 on the outdoor unit I/F PCB is "0", SW02 is "7" and 7-segment nixie tube display becomes "1..".
6. Back up running of TE sensor
When the TE sensor has fault, it will automatically enter into auxiliary running by fixing the value (20*)
of TE sensor.
The SW01 on the outdoor unit I/F PCB is "0", SW02 is "7" and 7-segment nixie tube display becomes
"..1".