96
FlexFit Pro
B.Static selection via wired controller:
1. Prepare: wired controller YR-E17, plug wired controller connector to indoor PCB CN3
2. Method:
2.1 In the state of ON and non screen saving state, press Fan + Set keys for 5s to enter static pressure grade
adjustment.
Press together and hold for 5
seconds
2.2 Static pressure icon will ash and the current setting will be displayed
2.3. Press key
to change static pressure grade N(1≤N≤10,integer), then press Set key to conrm.
Use these buttons to adjust static pressure
level numbers.
press Set key to conrm.