seconds, the compressor and water spraying motor turn off, other loads operate and
LED displays E4, the unit initiates the anti-frost protection function and the buttons are
inactive (except the OFF button). Once the pipe temperature rises to exceed or equal 8
℃, the protection is relieved, the original status is restored and the unit meets the
requirements for 3-minute delay protection of the compressor.
二. Full water protection function:
When the water in the water tray exceeds the alarm level, the unit will alarm
automatically and the full water indicator illuminates. In this case, you need to drain the
condensate in the unit; otherwise, the unit will shut down automatically after the buzzer
gives off 5 beeps. (For more information about the drain method, refer to the “Drain”). If
the unit is not shut down manually, the unit will be restored to the previous operating
status automatically once the water is fully drained. Or the power may be turned on
again to start the unit.
三. Delay protection function of the compressor
This unit offers restart protection for the compressor. Except that the compressor
may start immediately when the unit is energized for the first time, there is 3-minute
delay start protection after the compressor is shut down.
四.Disassembly Instrustions
Prior to disassembly the unit,make sure that the POWER is off and the power
cord is unplugged from the wall receptacle.
1.Mechanical parts
1.1 Discharge the front and rear panel
1.Remove the duct assembly.
2.Remove 4 pieces of filter