(4) Freezing prevention function
Under refrigerating and dehumidifying state, the air conditioner will control the
outdoor fan as per the temperature Tp of the indoor coil pipe according to the
following conditions:
Zone of return deference
Compressor,outdoor fan OFF after 5 minutes Fan,compressor ON
0 7 Tp(℃
.)
(5) 3 minutes stand-by time
When the compressor ceases due to the sensor OFF, unit On or OFF or fault, it
will maintain pause for 3 minutes.
(6) Compensatory function of power failure
If the unit is suddenly off during running due to power failure, or closed for
maintenance or troubleshooting, it will restart to run after the power resumes with
the original condition before the unit is off
Note: 1. Function setting: Pressing the SLEEP button on the remote control unit
for 10 times until hearing 4 sounds from the buzzer on the panel.
2. Memory content: Running mode, setting wind speed, setting
temperature, sleep state, flap state.
3. Cancellation of function: Pressing the SLEEP button on the remote
control unit for 10 times until hearing 2 sounds from the buzzer on the
panel.
(7) Trial run function
When the air conditioner is in OFF state, press the emergency switch for 5
seconds till hearing 2 sounds of click from the buzzer, then the air conditioner will
turn to the trial run state. The unit will run in the refrigerating mode and the
indoor fan will run in high wind speed mode.
(8) Emergency running mode
When the air conditioner is in stand-by state, press the emergency switch till
hearing a sound from the buzzer, then the air conditioner will turn to the
emergency run state. The rules of emergency run are as follows:
a. Tr≥23℃, running refrigerating mode, Ts = 26℃;
b. Tr<23℃, running fan only mode,.
Edition:2006/01/09