79
Long pipe and high drop
1. Allowable piping length and drop between indoor and outdoor
Outdoor is only one
L5
L6
L7 L8
L9
L10
L11
L12 L13
L14
L15
L16 L18
L20
L17 L19
L21
L22
V2
V1
A
B C D E
F
H2
H3
H
G
V3 V4
Outdoor 3
L3<10m
L1+L3<10m
L2+L3<10m
Note:
V1---V4: VP unit
A---F: indoors (coling / heating selection possible)
G---H: indoors (cooling only )
Outdoor 1
Outdoor 2
Over 200mm
Over 200mm
Below 2m
Below 2m
Outdoor 3
A
B
C
D
E F G
L1
L2
L3
L4
L5
L6 L7 L8 L9
L10
L11
L12 L13
L14
L15
L16 L18 L20
L22
H2
H3
H
L17 L19
L21
V1 V2 V3 V4
The outdoor is more than one unit
When the distance between outdoors(L1, L3) is over 2m, the oil trap must be set (upright
projecting pipe, 200mm high), as the gure :