- 115 -
54
55
56
57
63
64
Part 3
voltage is too low
20
20
20
20
20
20
digital
tube
indication
on master
unit
indication
on wired
controller
(hex)
failure code definition
failure description
DCCT faulty
incorrect wiring
52
53
20
20
radiator sensor failure
current sensor broken down
before startup, detect if the sensor is in short circuit or in
open circuit. 2 minutes and 50 seconds later after unit stops,
resume.
radiator fan broken down
69
20
before startup, the sensor is in short circuit or in open circuit.
2 minutes and 50 seconds later after unit stops, resume.
detecting VDC is less than 289V. 2 minutes and 50 seconds
later after unit stops, resume.
STANDBY state keeps for 10 minutes. 2 minutes and 50
seconds later after unit stops, resume.
in running, H/W of ACCT is faulty. 2 minutes and 50 seconds
later after unit stops, resume.
in running, H/W of ACCT is faulty. 2 minutes and 50 seconds
later after unit stops, resume.
ACCT faulty
58 20
IPM faulty
in running, IPM output is faulty. 2 minutes and 50 seconds
later after unit stops, resume.
59 20
VDC faulty
in running, H/W of VDC is faulty. 2 minutes and 50 seconds
later after unit stops, resume.
60 20
logic problem
when startup or running, PWM output is abnormal, 2 minutes
and 50 seconds later after unit stops, resume.
61 20
IPM in short circuit or the
earthing is short circuit
IPM in short circuit or earthing in short circuitl, 2 minutes
and 50 seconds later after unit stops, resume.
62 20
load is short circuit
load in short circuit, 2 minutes and 50 seconds later after
unit stops, resume.
ACCT wiring is faulty, 2 minutes and 50 seconds later after
unit stops, resume.
overload
current exceeds the limitation for 10 minutes, 2 minutes
and 50 seconds later after unit stops, resume.
65 20
DCCT sensor detecting
abnormal
in startup, DCCT current is less than 6.5A. 2 minutes and
50 seconds later after unit stops, resume.
66 20
DCCT sensor broken down
before startup, DCCT voltage is out of control. 2 minutes
and 50 seconds later after unit stops, resume.
no communication for 4 minutes
67 20
communication abnormal
with fan motor driving board
68 20
DC fan motor driving board
IPM alarms
in communication the code byte is 0*20. 2 minutes and 50
seconds later after unit stops, resume.If it occurs 3 times
in an hour, confirm the alarm.
DC fan motor driving board
pressure too high protection
in communication the code byte is 0*04. 2 minutes and 50
seconds later after unit stops, resume.If it occurs 3 times
in an hour, confirm the alarm.
70
20
DC fan motor driving board
pressure too low protection
in communication the code byte is 0*08. 2 minutes and 50
seconds later after unit stops, resume.If it occurs 3 times
in an hour, confirm the alarm.
71 20
DC fan motor driving board
blocked
in communication the code byte is 0*01. 2 minutes and 50
seconds later after unit stops, resume.If it occurs 3 times
in an hour, confirm the alarm.
72 20
DC fan motor driving board
EEPROM faulty
in communication the code byte is 0*02. 2 minutes and 50
seconds later after unit stops, resume.If it occurs 3 times
in an hour, confirm the alarm.
73 20
DC fan motor driving board
detecting out of control
in communication the code byte is 0*10. 2 minutes and 50
seconds later after unit stops, resume.If it occurs 3 times
in an hour, confirm the alarm.