- 61 -
5.2.2 Indoor central control address setting (necessary for the system with
central control or BMS control)
No.
setting
mode
setting method remark
1
central
controller
address
setting by
hand
1. “1” of SW02 on indoor PCB at
“ON” (up)
2. details about address and
dipswitch position please
refer to the following table.
setting
on site
2
central
controller
address
setting by
wired
controller
3. SW02 on indoor PCB are all
at “OFF” (down), that also is
the setting state when out of
factory.
4. press “filter reset” button for
10 seconds, then enter
central control setting mode,
choose indoor central
address by press “TEMP +/
-” button.
5. temp. display area displays:
system address +XX, then
press “TEMP +/-” button,
unit No. will change within
00~7F, (00 is No. 1, 7F is No.
128” ), original value is 00.
6. after the No. of units is
chosen, press “SET” button
to save all the setting. If you
press the other buttons, or no
any actions within 15
seconds, then the setting will
exit automatically and system
will keep the last time setting.
setting
on site