5.4.2 Indoor unit running data display
SW
3
SW
4
SW
5
function
definition
content
displayed on
digital tube
remark
0/1/
2/3
0
15
3
display the
indoor has
or has not
communicat
ion
“1111” means
the indoor
has
communicati
on
“----“ means
no
communicati
on
0/1/
2/3
0
15
4
display
failure code
of the indoor
unit
such as “1”, if
no failure it will
display “0”
0/1/
2/3
0
15
5
display
capacity of
the indoor
unit
such as “1.5”
0/1/
2/3
0
15
6
display
open angle
of the
indoor EEV
such as “280”
0/1/
2/3
0
15
7
display
return air
temp. of the
indoor unit
such as “28”
0/1/
2/3
0
15
8
display gas
pipe “TC1”
temp. of
indoor
such as “9”
0/1/
2/3
0
15
9
display
liquid pipe
“TC2” temp.
of indoor
such as “8”
1.dial SW03
to 0, it shows
running data
of indoor from
No.1 to No.16
2.Dial SW03
to 1, it shows
running data
of indoor from
No.17 to
No.32
3.Dial SW03
to 2, it shows
running data
of indoor from
No.33 to
No.48
4.Dial SW03
to 3, it shows
running data
of indoor from
No.49 to
No.64
Part 2