Haier MRV S II - High;Low Pressure Sensor Failure; Outdoor EEPROM Failure

Haier MRV S II
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6161
Troubleshooting
If sensor terminal is xed well
If voltage between red terminal
and black terminal is 5V when
testing pressure sensor by
multimeter
If voltage between white terminal and black
terminal is 0.5V~3.5V when testing pressure
sensor by multimeter
Replace connecting board
Reconnect
Reconnect
Replace PCB
Replace pressure sensor
No
No
No
No
Yes
Yes
Yes
Yes
If the EEPROM is xed well
Replace EEPROM
[28, 29] High/low pressure sensor failure
[33] Outdoor EEPROM failure