11
PP38+ Pellet Stove

This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
should be three to ve feet high and at least three
inches from a combustible wall. This vertical section
will provide natural draft in the event of a power failure.
If the stove is installed below grade be sure the
vent termination is at least 18" above grade. The outlet
must also be 1 foot from the house/building.
Note: Do not place joints within wall pass-
throughs.

This method provides excellent venting for normal
operation and allows the stove to be installed closest
to the wall. Two inches from the wall is safe; however,
four inches allows better access to remove the rear
panel. The vertical portion of the vent should be three
to ve feet high. This vertical section will help provide
natural draft in the event of a power failure. 


36" min
clearance to any
combustible
material
12" min. wall to outlet




Fig. 8





Fig. 9




