111 4000662720 E 06.17 USA / EN
C
- Study of the electric schematics
HA26 RTJ O - HA26 RTJ O SW - HA26 RTJ PRO - HA26 RTJ PRO SW - HA80 RTJ O - HA80 RTJ PRO
2.5.11 - Basket compensation
2.5.11.1 - Validation
REQUIREMENTS DEFINITION
PLV03
Platform level for up (U) and down (D) direction is inhibited if at least one of the following cut-off
conditions is active :
CUT-OFF U D GENERAL CUT-OFF CONDITIONS
1 General
1 1 1 Generator is running
2 1 1 Safety valves tool is active
311
Upper controls emergency stop pushed and
overriding mode not active
411
Delay to change fuel selection (dual fuel
engines only)
REQUIREMENTS DEFINITION
PLV03
CUT-OFF U D
SIMULTANEOUS MOVEMENTS CUT-OFF
CONDITIONS
2
Simultaneous
movements
1..8 1 1
Requirements SM_CE_03 | SM_AU_02 |
SM_ANSI_02
REQUIREMENTS DEFINITION
PLV03
CUT-OFF U D OVERLOAD CUT-OFF CONDITIONS
3 Overload 1 1 1 Overload alarm is active
REQUIREMENTS DEFINITION
PLV03
CUT-OFF U D TILT CUT-OFF CONDITIONS
4 Tilt N/A N/A N/A N/A
REQUIREMENTS DEFINITION
PLV03
CUT-OFF U D REACH LIMIT CUT-OFF CONDITIONS
5 Reach limit N/A N/A N/A N/A