90 4000662720 E 06.17 USA / EN
HA26 RTJ O - HA26 RTJ O SW - HA26 RTJ PRO - HA26 RTJ PRO SW - HA80 RTJ O - HA80 RTJ PRO
C
- Study of the electric schematics
2.5.3 - Drive
2.5.3.1 - Validation
REQUIREMENTS DEFINITION
DSV03
Forward (F) and/or reverse (R) drive motion is/are inhibited if at least one of the all cut-off condition is
activated :
CUT-OFF F R GENERAL CUT-OFF CONDITIONS
1 General
1 1 1 Generator is running
2 1 1 Maximum number of running movements is reached
3 1 1 Safety valves tool is active
4 1 1 Upper emergency stop pushed
511
Delay to change fuel selection (dual fuel engines
only)
REQUIREMENTS DEFINITION
DSV03
CUT-OFF F R
SIMULTANEOUS MOVEMENTS CUT-OFF
CONDITIONS
2
Simultaneous
movements
1..10 1 1
Requirements SM_CE_03 | SM_AU_02 |
SM_ANSI_02
REQUIREMENTS DEFINITION
DSV03
CUT-OFF F R OVERLOAD CUT-OFF CONDITIONS
3 Overload 1 1 1 Overload alarm is active
REQUIREMENTS DEFINITION
DSV03
CUT-OFF F R TILT CUT-OFF CONDITIONS
4 Tilt 1 1 1 Tilt activated with unfolded machine
REQUIREMENTS DEFINITION
DSV03
CUT-OFF F R REACH LIMIT CUT-OFF CONDITIONS
5 Reach limit N/A N/A N/A N/A