1030 HEIDENHAIN Technical Manual iTNC 530 HSCI
Save this value with the STORE MP2430.x soft key.
Press the END key to exit the Commission Current Controller mode.
If the overall result of commissioning a servo drive or an axis is unsatisfactory,
these recommendations do not need to be strictly followed. This may mean
that
Adjustment with overshoot is used to increase the current controller
bandwidth.
A higher PWM frequency is selected to increase the current controller
bandwidth.
The current controller bandwidth is reduced.
Axes: MP2430.x at optimum setting
Spindle: MP2430.x at optimum setting