July 2013 6.14 Commissioning 1045
Set to operation with following error.
Enter the following test program:
LBL2
L X <maximum traverse> R0 FMAX
L X0 R0 FMAX
CALL LBL1 REP 100/100
Start the test program.
Display the actual feed rate (v actual) with the internal oscilloscope:
• If no oscillations are recognizable, no kink point is required.
• If oscillations are visible, you must reduce MP1820.x until the oscillations
have disappeared.
MP1820.x at optimum setting
MP1820.x too small