1920 HEIDENHAIN Technical Manual iTNC 530 HSCI
Module 9103 Transmit string through data interface
You must first assign the interface to the PLC and initialize it with Module
9100.
Module 9103 transmits a string from a string memory through one of the two
interfaces. Links to the PLC error file and PLC dialog file are deleted.
Can only be called in a submit job or spawn job!
Call:
PS B/W/D/K <>Interface>
0: RS232
1: RS422
PS K/B/W/D <>Number of source string in the string buffer>
CM 9103
Error code:
Marker Value Meaning
M4203 0 String sent
1 Error code in W1022
W1022 1 Incorrect interface or incorrect string number
12 No string end found
13 Interface not ready
14 Interface not assigned
15 Transmit buffer not empty
20 Module was not called in a submit or spawn job