3.9.2 Double-row configuration
Components and cables for double-row configuration:
When using a double-row configuration, please keep the following in mind:
The litz wires used for the DC-link connection of the power modules in the
"second row" must not be longer than 3 m.
Litz wires with 16 mm² cross section make a DC-link current of approx. 67 A
possible. In a regenerative system, this results in approx. 35 kW of
continuous power for the system connected by these wires.
In a nonregenerative system the resulting maximum power is
approx. 25 kW.
Use fast-acting semiconductor fuses for protection of the UV(R) 1xxD on the
primary side.
The length of the unit bus ribbon cable must not exceed 1 m!
If necessary, place the MS 110 or MS 111 in the "second row" in the center
of the UMs.
When calculating the length of the ribbon cables, make sure to include the
module width of the MS 110 or MS 111.
Component/Cable ID
Unit bus cable (shielded, round) with 37-pin D-sub at both
ends; max. length: 3 m
ID 664023-xx
PWM cable (round) with ribbon connector at both ends;
max. length: 5 m
ID 664332-xx
Supply bus cable (round) with ribbon connector at both
ends; max. length: 5 m
(only necessary if the UV(R) 1xxD is not in the same row
as the CC/MC)
ID 361508-xx
Wire for DC-link (16 mm2, shielded, color: red); max.
length: 3 m
ID 655440-xx
Wire for DC-link (16 mm2, shielded, color: blue); max.
length: 3 m
ID 655438-xx