July 2013 3.10 UxC 11x (FS): Power supply and motor connection 261
X89: Braking
resistor
Connection at the UEC 11x:
On the UEC 11x compact inverters, there must be no bridge at connector X89.
A bridge at X89 would cause the internal braking resistor to be bridged and
lead to a short circuit of the DC-link voltage. If necessary, you can connect an
external braking resistor (PW 210) via X89 in parallel to the internal braking
resistor.
X90: 24 V
NC output
X344: 24 V supply
for motor holding
brakes
X394: Motor
holding brakes
Connecting
terminal X89
UE 11x
Assignment PW 21x PW 1x0(B);
connecting
terminal X1
1+U
Z
RB1 1
2 Switch to –U
Z
RB2 2
Connecting
terminal X90
Assignment
+ or terminal 1 +24 V NC (max. 3.5 A)
– or terminal 2 0 V
The interface is electrically separated (protective extra-low voltage (PELV)
as per EN 61800-5-1).
Connecting terminals Assignment
1 +24 V PLC
20 V PLC
Connecting terminals Assignment
1 Holding brake X80
20 V PLC
3 Holding brake X81
40 V PLC
5 Holding brake X82
60 V PLC
7 Holding brake X83
80 V PLC
9 Holding brake X84
10 0 V PLC