340 HEIDENHAIN Technical Manual iTNC 530 HSCI
The emergency stop inputs (pin 6 and pin 8) are active even if the HR
handwheel has been deactivated via machine parameter MP7640. It is
therefore always necessary to wire the emergency stop inputs correctly.
Emergency stop buttons are to be used exclusively for emergency stop
purposes. Under normal operating conditions, a machine must not be
switched off via the emergency stop buttons. The proper functioning of all
emergency stop buttons is to be tested annually by pressing these buttons.
General:
Key assignment for
machine operating
panel
Danger
Please note that the MB 720 is powered by +24 V NC.
For the entire HSCI system, the +24 V NC supply voltage is required to be
safely separated voltage. The +24 V NC supply voltage must not, under any
circumstances, be connected with the +24 V PLC supply voltage, because
this removes the double basic insulation.