514 HEIDENHAIN Technical Manual iTNC 530 HSCI
MP2195 Handling of status signals from HEIDENHAIN power supply
units. MP2195 can also be overwritten by the PLC and the
LSV2 protocol.
Input: Bit 0 – Status signals that are already active
during control power-up
0: Missing signals are ignored
1: Missing signals are evaluated
Bit 1– ERR.UZ.GR
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 2 – ERR.TMP
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 3 – Reserved
Bit 4 – ERR.IZ.GR
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 5 – RDY.PS signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 6 – ERR.ILEAK
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 7 - PF.PS.AC
0: Error message is not suppressed
1: Error message is suppressed
Bit 8 - PF.PS.DC
0: Error message is not suppressed
1: Error message is suppressed
Bit 9 – Monitoring the DC-link voltage Uz or LIFT-OFF
function
0: Uz monitoring and LIFTOFF function are active
1: Uz monitoring and LIFTOFF function are not active
Bit 10 – Power monitoring of the UV(R)
0: Monitoring active
1: Monitoring not active
PLC 924,
902
MP2196.x Identifier for power supply module in MP2198.x
Input: P, Q, R or T
PLC
RUN
1007
MP2198.x Type of power supply module
Input: Name from file SUPPLY.SPY
Default setting: Empty string
PLC
RUN
1007
MP2199.x Assignment of the drive to the power supply module
Input: 0: The axis/spindle is assigned to the UV in
MP2198.0
1: The axis/spindle is assigned to the UV in MP2198.1
PLC
RUN
1007
MP2200.x Motor model
Input: Name of the selected motor
(is entered by the iTNC)
PLC
RUN
1007
MP Function and input Software
version and
behavior
Page