July 2013 4.4 List of machine parameters 533
4.4.8 Configuration of the data interface
MP Function and input Software
version and
behavior
Page
MP5000 Disable data interfaces
Input: 0: No interface disabled
1: RS-232-C/V.24 interface disabled
2: RS-422/V.11 interface disabled
3: RS-232-C/V.24 and RS-422/V.11 interfaces disabled
PLC
RUN
1903
MP5020 Configuration of the data interface
Format: %xxxxxxxx
Input: Bit 0 –
0: 7 data bits
1: 8 data bits
Bit 1 –
0 : Any BCC character
1 : BCC not control character
Bit 2 –
0: Transmission stop by RTS not active
1: Active
Bit 3 –
0: Transmission stop by DC3 not active
1: Active
Bit 4 –
0: Character parity even
1: Odd
Bit 5 –
0: Character parity not desired
1: Desired
Bit 6 = 0, Bit 7 = 0: 1.5 stop bits
Bit 6 = 1, Bit 7 = 0: 2 stop bits
Bit 6 = 0, Bit 7 = 1: 1 stop bit
Bit 6 = 1, Bit 7 = 1: 1 stop bit
Bit 8, 9 – Reserved
Bit 10 –
Check for missing connection
0: Active
1: Not active
PLC
RUN
CN123
1905
MP5020.0 Operating mode EXT1
MP5020.1 Operating mode EXT2
MP5020.2 Operating mode EXT3 (PLC)
MP5020.3 Operating mode EXT4 (PLC)