68 HEIDENHAIN Technical Manual iTNC 530 HSCI
Module 9288 Status requests regarding a VNC client
PLC Module 9288 (call only from within a submit/spawn job) is used to
program the following status requests regarding control and assignment of
multiple operator terminals (IPC):
Properties of a client (master / can be master / can be displayed)
Constraints:
Call only from a submit/spawn job.
The names of the clients (host name or MAC address) can be ascertained
with Module 9287.
Call:
PS B/W/D/K <Mode>
0: Properties of the ThinClient
PS B/W/D/K <Name>
PLC string with name of the client
PS B/W/D/K <Timeout [ms]>
Module rounds up to the next 100 ms limit
0: Default timeout 3000 ms
PS B/W/D/K <Additional parameter 1>
Mode 0: - - -
CM 9288
PL B/W/D <Error code>
0: No error
1: PLC error, error code in PLC error word (see below)
>= 100: Operating-system error
PL B/W/D <Status>
Mode 0:
Bit 0: 1 = Client is master
Bit 1: 1 = Client can be master
Bit 2: 1 = Client can be displayed