838 HEIDENHAIN Technical Manual iTNC 530 HSCI
To use feedback control with velocity semifeedforward:
Activate the velocity feedforward control with MP1391 and/or MP1392.
Determine the k
v
factor for velocity feedforward control (MP1510.x).
Activate the velocity semifeedforward control by entering the desired factor
in MP1396.x.
Determine the k
v
factor for velocity semifeedforward control (MP1516.x).
Enter MP1396.x = 1 to return to velocity feedforward control.
For example, you may now use FN17: SYSWRITE ID 600 in an OEM cycle
to overwrite or reestablish the factor in MP1396.x.
MP1396.x Feedback control with velocity semifeedforward
Input: 0.001 to 0.999
1: Velocity feedforward control
MP1516.x kv Factor for velocity semifeedforward
Input: 0.100 to 20.000 [(m/min)/mm]
Set Reset
M4625 Disable NC axes when velocity
semifeedforward control is active
PLC PLC